Honeywell 301IRF Refrigerant Gas Detector for Chiller Rooms
Refrigerant Gas Detection · 301IRFThe Honeywell 301IRF is an infrared refrigerant gas detector designed for at-the-source detection in chiller and mechanical rooms. Its low-profile, rugged ABS-polycarbonate housing mounts directly on the chiller pad or low on a nearby wall, where heavier-than-air refrigerants collect, giving early warning of a leak. The detector covers 0 to 1,000 ppm and responds to a broad list of refrigerants, including R11, R22, R123, R125, R134A, R404A, R407C, R410A, R448A, R449A, R507A, R513A, R514A, 1233ZD and 1234ZE. Accuracy is ±40 ppm at 500 ppm, and an LED indicator shows status locally. The 301IRF is installed with the 301EM-20 mechanical room controller, which can switch exhaust fans, horns and strobes automatically on a leak, as well as manual fan control. Together they provide a solution for ASHRAE 15 and CSA B-52 mechanical room requirements. The detector runs on 12 VDC, operates in 0 to 95% RH non-condensing conditions and needs a 15-minute warm-up.
Price on requestFor quote